橫河AAP135-S00脈沖輸入模塊
AAT145-SE3/13S10 AAI135-SE3/13S10 AAI835-SE3/13S10 AAR145-SE3/13S10 AAI543-HF3/A4S10
AAT145-SF3/13S10 AAI135-SF3/13S10 AAI835-SF3/13S10 AAR145-SF3/13S10 AAI543-S00/A4D00
AAT145-H03/13S10 AAI135-H03/13S10 AAI835-H03/13S10 AAR145-H03/13S10 AAI543-S50/A4D00
AAT145-H53/13S10 AAI135-H53/13S10 AAI835-H53/13S10 AAR145-H53/13S10 AAI543-S60/A4D00
AAT145-H63/13S10 AAI135-H63/13S10 AAI835-H63/13S10 AAR145-H63/13S10 AAI543-SE0/A4D00
Pulse Input Module (Isolated Channels)
This module receives contact ON/OFF, voltage pulse and current pulse. This is isolated between the ?eld and the system as well as between each channel.
It can be used in dual redundant con?guration.
AAP135-S00脈沖輸入模塊
Items | Speci?cations |
Model | AAP135 |
Number of input channels | 8, isolated channels |
Input signal (*3) | 2-wire type: Contact ON/OFF, voltage pulse, current pulse (possible to supply transmitter power supply) 3-wire type: Power-supply-type voltage pulse |
Input frequency | 0 to 10 kHz (*4) |
Withstanding voltage | Between input and system: 500 V AC, For 1 minute Between channels: 500 V AC, For 1 minute (*1) |
Minimum input pulse width | 40 µs |
Input signal level | Contact input Open/close levels of relay contact and transistor contact Open: 100 kΩ or more, Close: 200 Ω or less Contact capacity When supplying 12 V DC: 15 V DC 15 mA or more When supplying 24 V DC: 30 V DC 30 mA or more Voltage/current pulse input (Current input is converted to voltage.) VH (high level): 3 to 24 V DC VL (low level): -1 to 8 V DC VH-VL (swing value): 3 V or more Signal source resistance: 1 kΩ or less |
Shunt resistance | Can be selected from none/200/500/1000 Ω. (Open when power is OFF and for the standby side in a dual-redundant con?guration) |
Pull-up resistance | 68 kΩ (12 V DC or 24 V DC) |
Filter | Filter for eliminating chattering can be set. (*2) |
Data update period | 2 ms |
Transmitter power supply | Can select 24 V DC/12 V DC. Limiter value 12 V DC ±10 %: 40 mA, 24 V DC ±10 %: 30 mA |
Maximum current consumption | 300 mA (5 V DC), 400 mA (24 V DC) |
Weight | 0.3 kg |
External connection | Pressure clamp terminal, KS cable, MIL connector cable |
AAP135-S00脈沖輸入模塊
*1: The withstanding voltage for using MIL connector cable depends on the electrical speci?cations of its cable.
*2: When the pulse input signal is dry contact (such as from a mechanical relay) up to 10 Hz, it is possible to eliminate the chattering.
*3: The connection method of the ?eld devices varies depending on the input signal.
For details, please refer to Installation Guidance (TI 33M01J10-40E).