參考價(jià): | 面議 |
- 產(chǎn)品型號(hào)
- 品牌
- 經(jīng)銷(xiāo)商 廠商性質(zhì)
- 上海市 所在地
訪問(wèn)次數(shù):318更新時(shí)間:2017-10-18 18:17:12
西門(mén)子972-0BB41-0XA0 西門(mén)子972-0BB41-0XA0
possible to connect the following bus connectors to the MPI interface: With socket: 6ES7 972-0BB42-0XA0 Without socket: 6ES7 972-0BA42-0XA0 Mode selector switch: Toggle switch design. Diagnostic buffer: The last 120 fault and interrupt events...? css/ted.css The CPU 417-4 features: Powerful processor: The CPU achieves command execution times as low as0.018 µs per binary instruction. 32 MB work memory (of which 16 MB each for program and data); faster work memory for sections | ||||
|
SIPLUS CPU 417-4
- 訂貨數(shù)據(jù)
- 附件
- 產(chǎn)品信息
- 組態(tài)工具
跳轉(zhuǎn)到
概述
應(yīng)用
設(shè)計(jì)
技術(shù)規(guī)范
概述
強(qiáng)大的 SIMATIC S7-400 CPU
- 適用于對(duì)性能要求很高的工廠
- 帶兩個(gè) IF 模塊的插槽
注:
SIPLUS extreme 產(chǎn)品基于 SIMATIC 標(biāo)準(zhǔn)產(chǎn)品。此處列出的內(nèi)容來(lái)自相關(guān)的標(biāo)準(zhǔn)產(chǎn)品。添加了特定 SIPLUS extreme 信息。
有關(guān) SIPLUS 的技術(shù)文檔,可訪問(wèn):
http://www.siemens.de/siplus-extreme
應(yīng)用
The CPU 417-4 is the most powerful SIMATIC S7-400 CPU. The integral PROFIBUS DP interfaces permit direct connection to the PROFIBUS DP fieldbus as master or slave.
Two further DP master systems can be connected via the IF 964-DP interface submodules.
Note:
Only the interface module 6ES7 964-2AA04-0AB0 can be used.
設(shè)計(jì)
CPU 417-4 的特性:
- 強(qiáng)大的處理器:
CPU 執(zhí)行每條二進(jìn)制指令時(shí)間僅為 0.018 µs。 - 32 MB 工作存儲(chǔ)器(程序和數(shù)據(jù)各 16 MB);
快速工作存儲(chǔ)器用于對(duì)于執(zhí)行十分重要的用戶(hù)程序部分。 - 可靈活擴(kuò)展:
zui多 262 144 點(diǎn)數(shù)字量輸入/輸出和 16 384點(diǎn)模擬量輸入/輸出 - MPI 多點(diǎn)接口:
通過(guò) MPI,可方便地將zui多 32 個(gè)站聯(lián)成網(wǎng)絡(luò),數(shù)據(jù)傳輸速率可高達(dá) 12 Mbit/s。該 CPU 可與通信總線 (C-bus) 和 MPI 的站之間建立zui多 44 個(gè)連接。
注意:
如果 PROFIBUS DP 接口和 MPI 接口同時(shí)運(yùn)行,那么只能將以下總線連接器連接到 MPI 接口:- 帶插口:6ES7 972-0BB42-0XA0
- 不帶插口:6ES7 972-0BA42-0XA0
- 模式選擇開(kāi)關(guān):
撥位開(kāi)關(guān)設(shè)計(jì)。 - 診斷緩沖區(qū):
zui后的 120 個(gè)故障和中斷事件保存在一個(gè)環(huán)形緩沖器中,用于進(jìn)行診斷(可擴(kuò)展)。 - 實(shí)時(shí)時(shí)鐘:
CPU 的診斷報(bào)警帶有日期和時(shí)間標(biāo)記。 - 存儲(chǔ)卡:
用于擴(kuò)展內(nèi)置裝載存儲(chǔ)器。存儲(chǔ)在裝載存儲(chǔ)器中的信息包括 S7?400 參數(shù)數(shù)據(jù)以及程序,因此需要 2 倍的存儲(chǔ)空間。其結(jié)果是:- 內(nèi)置的裝載存儲(chǔ)器不能滿(mǎn)足大程序量的要求,因此需要存儲(chǔ)卡。
可使用 RAM 和 FEPROM 卡(FEPROM 卡用于保持性存儲(chǔ))。
- 內(nèi)置的裝載存儲(chǔ)器不能滿(mǎn)足大程序量的要求,因此需要存儲(chǔ)卡。
- PROFIBUS DP 接口:
通過(guò) PROFIBUS DP 主站接口,可以實(shí)現(xiàn)分布式自動(dòng)化組態(tài),從而提高了速度,便于使用。對(duì)用戶(hù)來(lái)說(shuō),分布式 I/O 單元可作為一個(gè)集中式單元來(lái)處理(相同的組態(tài)、編址和編程)。
混合組態(tài):SIMATIC S5,SIMATIC S7 為 PROFIBUS 主站,符合 EN 50170 標(biāo)準(zhǔn)。
注:
當(dāng)同時(shí)使用 PROFIBUS DP 和 MPI 接口時(shí),只能將下列總線連接器連接到 MPI 接口:- 帶插口:6ES7 972-0BB42-0XA0
- 不帶插口:6ES7 972-0BA42-0XA0
- 兩個(gè)附加插槽:
可用 IF 964-DP 接口子模塊連接兩個(gè)附加的 PROFIBUS DP主站系統(tǒng)。
- Block protection:
a password concept also protects the user program from unauthorized access - Integrated HMI services:
The user only has to specify the source and destination of the data with HMI devices. The data are then transported cyclically and automatically by the system. - Integrated communication functions:
- PG/OP communication
- Global data communication
- S7 standard communication
- S7 communication
Configurable Attributes
The STEP 7 tool "Hardware configuration" can be used to program the properties and response of the S7-400 including the CPUs, e.g.
- Multipoint interface MPI:
- Definition of node addresses
- Startup/cycle behavior
- Stipulation of the maximum cycle time and communication load
- Address allocation:
Addressing of I/O modules - Retentive area:
Definition of the number of retentive bit memories, counters, timers, data blocks, and clock memories - Size of the process image, local data
- Length of the diagnostics buffer
- Protection level:
Definition of access authorizations to program and data - System diagnostics:
Definition of the handling and scope of diagnostics messages - Timed interrupts:
Setting of periods - Configuring
Reporting functions
- Status and fault indicators:
LEDs indicate internal and external faults and operating modes such RUN, STOP, restart, test function, etc. - Test functions:
The PG can be used to display signal states in program execution, modify process tags irrespective of the user program, read out the contents of stack memories, run separate program steps and inhibit program components. - Information functions:
The PG can be used to provide the user with information about the memory capacity and operating mode of the CPU, and the current utilization of the working and load memories.
技術(shù)規(guī)范
Article number | 6AG1417-4XT07-7AB0 | |
---|---|---|
| SIPLUS S7-400 CPU 417-4 V7 | |
General information |
| |
Product type designation | CPU 417-4 | |
Hardware product version | 01 | |
Firmware version | V7.0 | |
Engineering with |
| |
| STEP 7 V5.4 or higher with HSP 261 | |
CiR – Configuration in RUN |
| |
CiR synchronization time, basic load | 60 ms | |
CiR synchronization time, time per I/O byte | 7 µs | |
Supply voltage |
| |
Rated value (DC) |
| |
| No; Power supply via system power supply | |
Input current |
| |
from backplane bus 5 V DC, typ. | 1.3 A | |
from backplane bus 5 V DC, max. | 1.6 A | |
from backplane bus 24 V DC, max. | 600 mA; 150 mA per DP interface | |
from interface 5 V DC, max. | 90 mA; At each DP interface | |
Power loss |
| |
Power loss, typ. | 6.5 W | |
Power loss, max. | 8 W | |
Memory |
| |
Type of memory | RAM | |
Work memory |
| |
| 32 Mbyte | |
| 16 Mbyte | |
| 16 Mbyte | |
| No | |
Load memory |
| |
| Yes; with Memory Card (FLASH) | |
| 64 Mbyte | |
| 1 Mbyte | |
| Yes; with Memory Card (RAM) | |
| 64 Mbyte | |
Backup |
| |
| Yes | |
| Yes; all data | |
| No | |
Battery |
| |
Backup battery |
| |
| 225 µA; up to 40 °C | |
| 1 275 µA | |
| See reference manual, module data, Chapter 3.3 | |
| 5 V DC to 15 V DC | |
CPU processing times |
| |
for bit operations, typ. | 7.5 ns | |
for word operations, typ. | 7.5 ns | |
for fixed point arithmetic, typ. | 7.5 ns | |
for floating point arithmetic, typ. | 15 ns | |
CPU-blocks |
| |
DB |
| |
| 16 000; Number range: 1 to 16000 | |
| 64 kbyte | |
FB |
| |
| 8 000; Number range: 0 to 7999 | |
| 64 kbyte | |
FC |
| |
| 8 000; Number range: 0 to 7999 | |
| 64 kbyte | |
OB |
| |
| see instruction list | |
| 64 kbyte | |
| 1; OB 1 | |
| 8; OB 10-17 | |
| 4; OB 20-23 | |
| 9; OB 30-38 (shortest cycle that can be set = 500 µs) | |
| 8; OB 40-47 | |
| 3; OB 55-57 | |
| 4; OB 61-64 | |
| 1; OB 60 | |
| 1; OB 90 | |
| 3; OB 100-102 | |
| 9; OB 80-88 | |
| 2; OB 121, 122 | |
Nesting depth |
| |
| 24 | |
| 2 | |
Counters, timers and their retentivity |
| |
S7 counter |
| |
| 2 048 | |
Retentivity |
| |
| Yes | |
| 0 | |
| 2 047 | |
| Z 0 to Z 7 | |
Counting range |
| |
| 0 | |
| 999 | |
IEC counter |
| |
| Unlimited (limited only by RAM capacity) | |
S7 times |
| |
| 2 048 | |
Retentivity |
| |
| Yes | |
| 0 | |
| 2 047 | |
| No times retentive | |
Time range |
| |
| 10 ms | |
| 9 990 s | |
IEC timer |
| |
| Yes | |
| SFB | |
| Unlimited (limited only by RAM capacity) | |
Data areas and their retentivity |
| |
retentive data area in total | Total working and load memory (with backup battery) | |
Flag |
| |
| 16 kbyte; Size of bit memory address area | |
| Yes | |
| MB 0 to MB 15 | |
| 8; in 1 memory byte | |
Data blocks |
| |
| 16 000; Number range: 1 to 16000 | |
| 64 kbyte | |
Local data |
| |
| 64 kbyte | |
| 32 kbyte | |
Address area |
| |
I/O address area |
| |
| 16 kbyte | |
| 16 kbyte | |
of which distributed |
| |
| 2 kbyte | |
| 2 kbyte | |
| 8 kbyte | |
| 8 kbyte | |
Process image |
| |
| 16 kbyte | |
| 16 kbyte | |
| 1 024 byte | |
| 1 024 byte | |
| 244 byte | |
| Yes | |
Subprocess images |
| |
| 15 | |
Digital channels |
| |
| 131 072 | |
| 131 072 | |
| 131 072 | |
| 131 072 | |
Analog channels |
| |
| 8 192 | |
| 8 192 | |
| 8 192 | |
| 8 192 | |
Hardware configuration |
| |
Number of expansion units, max. | 21 | |
connectable OPs | 119 | |
Multicomputing | Yes; 4 CPUs max. (with UR1 or UR2) | |
Interface modules |
| |
| 6 | |
| 6 | |
| 4; IM 463-2 | |
Number of DP masters |
| |
| 2 | |
| 10; CP 443-5 Extended | |
| 4 | |
| No; IM 467 cannot be used jointly with CP 443-5 Ext. or CP 443-1 in PROFINET IO mode | |
| 2 | |
| 6 | |
Number of IO Controllers |
| |
| 0 | |
| 4; Max. 4 in the central controller; no mixed operation of different CP 443-1 types in PROFINET IO mode | |
Number of operable FMs and CPs (recommended) |
| |
| Limited by number of slots and number of connections | |
| CP 440: Limited by number of slots; CP 441: limited by number of connections | |
| 14; Of which 10 CPs max. or IMs as DP master, 4 PROFINET controller maximum | |
Slots |
| |
| 2 | |
Time of day |
| |
Clock |
| |
| Yes | |
| Yes | |
| 1 ms | |
| 1.7 s; Power off | |
| 8.6 s; For power On | |
Operating hours counter |
| |
| 16 | |
| 0 to 15 | |
| SFCs 2, 3 and 4: 0 to 32767 hours SFC 101: 0 to 2^31 - 1 hours | |
| 1 hour | |
| Yes | |
Clock synchronization |
| |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
| No; Via CP | |
| Yes | |
Time difference in system when synchronizing via |
| |
| 200 ms | |
Interfaces |
| |
Interfaces/bus type | 1 x MPI/PROFIBUS DP, 1 x PROFIBUS DP, 2 x PROFIBUS DP (optionally pluggable) | |
Number of RS 485 interfaces | 2; Combined MPI / PROFIBUS DP and PROFIBUS DP | |
Number of other interfaces | 2; PROFIBUS DP with IF 964-DP (plug-in option; MLFB: 6ES7964-2AA04-0AB0) | |
1. Interface |
| |
Interface type | Integrated | |
Physics | RS 485 / PROFIBUS + MPI | |
Isolated | Yes | |
Power supply to interface (15 to 30 V DC), max. | 150 mA | |
Number of connection resources | MPI: 44, DP: 32 | |
Functionality |
| |
| Yes | |
| Yes | |
| Yes | |
MPI |
| |
| 44; If a diagnostics repeater is used on the line, the number of connection resources on the line is reduced by 1 | |
| 12 Mbit/s | |
Services |
| |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
DP master |
| |
| 32; If a diagnostics repeater is used on the line, the number of connection resources on the line is reduced by 1 | |
| 12 Mbit/s | |
| 32 | |
Services |
| |
| Yes | |
| Yes; S7 routing | |
| No | |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
Address area |
| |
| 2 kbyte | |
| 2 kbyte | |
User data per DP slave |
| |
| 244 byte | |
| 244 byte | |
| 244 byte | |
| 244 | |
| 128 byte | |
DP slave |
| |
| 32 | |
| http://support.automation.siemens.com/WW/view/en/113652 | |
| 12 Mbit/s | |
| No | |
| 32; Virtual slots | |
| 32 byte | |
| 32 byte | |
Services |
| |
| Yes; with interface active | |
| Yes; with interface active | |
| No | |
| No | |
| Yes | |
| Yes | |
| Yes | |
| No | |
| No | |
Transfer memory |
| |
| 244 byte | |
| 244 byte | |
2. Interface |
| |
Interface type | Integrated | |
Physics | RS 485 / PROFIBUS | |
Isolated | Yes | |
Power supply to interface (15 to 30 V DC), max. | 150 mA | |
Number of connection resources | 32 | |
Functionality |
| |
| Yes | |
| Yes | |
DP master |
| |
| 32 | |
| 12 Mbit/s | |
| 125 | |
Services |
| |
| Yes | |
| Yes; S7 routing | |
| No | |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
Address area |
| |
| 8 kbyte | |
| 8 kbyte | |
User data per DP slave |
| |
| 244 byte | |
| 244 byte | |
| 244 byte | |
| 244 | |
| 128 byte | |
DP slave |
| |
| 32 | |
| http://support.automation.siemens.com/WW/view/en/113652 | |
| 12 Mbit/s | |
| 32 | |
| 32 byte | |
| 32 byte | |
Services |
| |
| Yes; with interface active | |
Transfer memory |
| |
| 244 byte | |
| 244 byte | |
3. Interface |
| |
Interface type | Pluggable interface module (IF), technical data as for 2nd interface | |
Plug-in interface modules | IF 964-DP (MLFB: 6ES7964-2AA04-0AB0) | |
Physics | RS 485 / PROFIBUS | |
Isolated | Yes | |
Power supply to interface (15 to 30 V DC), max. | 150 mA | |
automatic detection of transmission rate | No | |
Number of connection resources | 32 | |
Functionality |
| |
| No | |
| Yes | |
| Yes | |
DP master |
| |
Services |
| |
| Yes | |
| Yes; S7 routing | |
| No | |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
Address area |
| |
| 8 kbyte | |
| 8 kbyte | |
User data per DP slave |
| |
| 244 byte | |
| 244 byte | |
| 244 byte | |
| 244 | |
| 128 byte | |
DP slave |
| |
| 32 | |
| http://support.automation.siemens.com/WW/view/en/113652 | |
| 12 Mbit/s | |
| 32 | |
| 32 byte | |
| 32 byte | |
Services |
| |
| Yes | |
| Yes; with interface active | |
| No | |
| No | |
| Yes | |
| Yes | |
| Yes | |
| No | |
| No | |
Transfer memory |
| |
| 244 byte | |
| 244 byte | |
4. Interface |
| |
Interface type | Pluggable interface module (IF), technical data as for 2nd interface | |
Plug-in interface modules | IF 964-DP (MLFB: 6ES7964-2AA04-0AB0) | |
Open IE communication |
| |
| Via CP 443-1 and loadable FB | |
| 1452 bytes via CP 443-1 Adv. | |
Isochronous mode |
| |
Isochronous operation (application synchronized up to terminal) | Yes; For PROFIBUS only | |
Equidistance | Yes | |
Number of DP masters with isochronous mode | 4 | |
User data per isochronous slave, max. | 244 byte | |
shortest clock pulse | 1 ms; 0.5 ms without use of SFC 126, 127 | |
max. cycle | 32 ms | |
Communication functions |
| |
PG/OP communication | Yes | |
| 119 | |
| 119; When using Alarm_S/SQ and Alarm_D/DQ | |
Data record routing | Yes | |
Global data communication |
| |
| Yes | |
| 16 | |
| 16 | |
| 32 | |
| 54 byte | |
| 1 variable | |
S7 basic communication |
| |
| Yes | |
| 76 byte | |
| 1 variable | |
S7 communication |
| |
| Yes | |
| Yes | |
| Yes | |
| 64 kbyte | |
| 462 byte; 1 variable | |
S5 compatible communication |
| |
| Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5 | |
| 8 kbyte | |
| 240 byte | |
| 64/64 | |
Standard communication (FMS) |
| |
| Yes; Via CP and loadable FB | |
Web server |
| |
| No | |
Number of connections |
| |
| 120 | |
| 119 | |
| 1 | |
| 0 | |
| 119 | |
| 1 | |
| 0 | |
| 118 | |
| 0 | |
| 0 | |
| 118 | |
| 0 | |
| 0 | |
| 59 | |
| 0 | |
| 0 | |
S7 message functions |
| |
Number of login stations for message functions, max. | 119; Max. 119 with Alarm_S/SQ and Alarm_D/DQ (OPs); max. 16 with Alarm, Alarm_8, Alarm_8P, Notify and Notify_8 (e.g. WinCC) | |
Symbol-related messages | Yes | |
SCAN procedure | Yes | |
Block related messages | Yes | |
Process diagnostic messages | Yes | |
simultaneously active Alarm-S blocks, max. | 1 000; Simultaneously active alarm_S/SQ blocks or alarm_D/DQ blocks | |
Alarm 8-blocks | Yes | |
| 10 000 | |
| 1 200 | |
Process control messages | Yes | |
Number of archives that can log on simultaneously (SFB 37 AR_SEND) | 64 | |
Number of messages |
| |
| 1 024 | |
| 128 | |
| 512 | |
| 1 024 | |
Number of additional values |
| |
| 1 | |
| 10 | |
Test commissioning functions |
| |
Status block | Yes; Up to 16 simultaneously | |
Single step | Yes | |
Number of breakpoints | 16 | |
Status/control |
| |
| Yes; Up to 16 variable tables | |
| Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters | |
| 70; Status/control | |
Forcing |
| |
| Yes | |
| Inputs, outputs, bit memories, peripheral inputs, peripheral outputs | |
| 512 | |
Diagnostic buffer |
| |
| Yes | |
| 3 200 | |
| Yes | |
| 120 | |
Service data |
| |
| Yes | |
Standards, approvals, certificates |
| |
CE mark | Yes | |
EAC (formerly Gost-R) | Yes | |
Ambient conditions |
| |
Ambient temperature during operation |
| |
| -25 °C; = Tmin | |
| 70 °C; = Tmax | |
Extended ambient conditions |
| |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | |
Relative humidity |
| |
| 100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation | |
Resistance |
| |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request | |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Configuration |
| |
Configuration software |
| |
| Yes | |
Programming |
| |
| see instruction list | |
| 7 | |
| Yes | |
| see instruction list | |
| see instruction list | |
Programming language |
| |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
| Yes | |
Number of simultaneously active SFCs |
| |
| 2; SFC 11; per interface | |
| 8; SFC 12; per interface | |
| 8; SFC 59; per interface | |
| 8; SFC 58; per interface | |
| 8; SFC 55; per interface | |
| 1; SFC 57; per interface | |
| 2; SFC 56; per interface | |
| 8; SFC 13; per interface | |
| 8; SFC 51 | |
| 1; SFC 103; per interface | |
Number of simultaneously active SFBs |
| |
| 8; SFB 52; per interface, but not more than 32 across all external interfaces | |
| 8; SFB 53; per interface, but not more than 32 across all external interfaces | |
Know-how protection |
| |
| Yes | |
| Yes; With S7 block Privacy | |
Dimensions |
| |
Width | 50 mm | |
Height | 290 mm | |
Depth | 219 mm | |
Weights |
| |
Weight, approx. | 900 g
|